FMU42-AMB2A22A
$0.00
Descripción
Measuring principle
Ultrasonic
Characteristic / Application
Compact ultrasonic transmitter
Supply / Communication
2-wire HART
Precisión
+/- 4 mm or +/- 0,2 % of set measuring range
Ambient temperature
-40 °C … 80 °C
(-40 °F … 176 °F)
Temperatura de proceso
-40 °C … 80 °C
(-40 °F … 176 °F)
Process pressure / max. overpressure limit
0.7 bar … 2.5 bar abs
(10 psi … 36 psi)
Main wetted parts
PVDF
Process connection
Flange
DN80, ASME 3″, JIS 10K 80
DN100,ASME 4″, JIS 10K 100
Mounting bracket
Blocking distance
0.4 m (1.3 ft)
Max. measurement distance
Liquids: 10 m (33 ft),
Solids: 5 m (16 ft)
Communication
4…20 mA HART
Certificates / Approvals
ATEX, FM, CSA, IEC, INMETRO, NEPSI
Application limits
Foam / high turbulence possible:
FMU44/FDU92
Fast filling and discharging
rate:
FMU90 + FDU9x
Level limit detection
FMU90 + FDU9x